Magellan MG5000 Manuel d'installation Page 9

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 56
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 8
MG5000 5
2.5 Auxiliary Power Terminals
The auxiliary power supply terminals can be used to power motion detectors, keypads and other modules or accessories in the
security system. A fuseless circuit protects the power supply against current overload and automatically shuts down if the current
exceeds 1.1A. If this occurs, the Maximum Auxiliary Current failure will appear in the keypad’s trouble display (see Trouble
Display on page 46). Therefore, the combined current consumption of devices connected to the auxiliary power supply should not
exceed 700mA. If the auxiliary output is overloaded and is shut down, you must disconnect all loads from the output for at least
10 seconds before reconnecting any load back to the auxiliary output.
2.6 Telephone Line Connection
In order to report system events to the monitoring station, you must connect the incoming telephone company wires into the TIP
and RING connections of the control panel and then run the wires from T1 and R1 to the telephone or telephone system as
shown in Figure 2 on page 3.
2.7 Bell Output Connection
The BELL+ and BELL- terminals power bells, sirens and other warning devices requiring a steady voltage output during an alarm.
The bell output supplies 12Vdc upon alarm and can support one 30-watt or two 20-watt sirens. The bell output uses a fuseless
circuit and will automatically shut down if the current exceeds 3A. When this occurs the Maximum Bell Current failure will only
appear in the keypad’s trouble display (see Trouble Display on page 46) during an alarm. If the load on the BELL terminals
returns to normal, the control panel will re-instate power to the BELL terminals during the next alarm. When connecting sirens,
please verify correct polarity. Connect the positive lead to the BELL+ terminal and the negative lead to the BELL- terminal of the
control panel as shown in Figure 2 on page 3.
If the BELL output is not being used, the Bell Disconnected failure will remain in the keypad’s trouble display
(see Trouble Display on page 46). To avoid this connect a 1K resistor across the BELL terminals.
For connection of a self-contained bell/siren, see Figure 2 on page 3.
2.8 Programmable Output Connections
When a specific event occurs in the system, a PGM can reset smoke detectors, activate strobe lights, open/close garage doors
and much more.
2.8.1 PGMs
The Magellan MG5000 control panel includes two on-board programmable outputs (PGMs). For details on how to
program PGMs, see Programmable Outputs on page 40. PGM1 and PGM2 can support up to 150mA. The PGMs are
limited by the power source being used. If powered by:
The
AUX terminals. The current consumption of the AUX terminals cannot exceed 700mA. Therefore, whatever
devices are connected to the AUX terminals (i.e. modules and PGMs) cannot exceed 700mA combined. For
example, if there are six modules connected to the AUX terminals that are using 600mA and you wish to power the
PGM using the
AUX terminals, the PGM’s current consumption cannot exceed 100mA.
An external power supply. If using an external power supply, the current consumption cannot exceed 150mA for
PGM1 and PGM2. If the external power supply’s current consumption limit is less than that of the PGM it is
connected to, than the current consumption will not exceed the power supply’s current limit.
UL Note: The AUX terminals cannot exceed 200mA for UL installations.
Figure 4: Relay and PGM Connections
Vue de la page 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 55 56

Commentaires sur ces manuels

Pas de commentaire