14 Reference & Installation Manual
Part 5: Zone Programming
When programming zones, the zone assignments are dependent on the designation of the wireless transmitters, assignment of keypad
zones, and the detection devices that are connected to the panel. For wireless assignment, see Wireless Transmitter Programming on
page 20 or the Installer Quick Menu of the MG5000 Programming Guide. For keypad assignment, see Configuring the Keypad Zone
Number on page 10. For panel hardwire detection devices, Table 3 on page 14. After assigning the required zones, you must set the zone’s
definitions, partition assignment, and options see Figure 9 on page 14. Certain Zone Definitions change if a Stay/Sleep alarm delay is
activated (section [720]). See Table 4 on page 17.
Table 3: Zone Recognition Table
If a zone is already programmed and you assign a device to the same zone, a wireless zone will overwrite a keypad/hardwire zone,
and a keypad zone will overwrite a hardwire zone.
Figure 9: Magellan Zone Programming
5.1 Zone Definitions
As demonstrated in Figure 6 above, sections [001] to [032] represent zones 1 through 32 respectively, where the first two digits
in each of these sections represents the zone's definition. To disable a zone, enter [00]. There are 21 available Zone Definitions.
5.1.1 Entry Delay 1 Zones
Sections [001] to [032]: Zones 1 to 32, First Digits = 01
When the system is armed and a zone defined with Entry Delay 1 opens, the control panel will generate an alarm after
the programmed Entry Delay 1 Timer elapses. This is to provide users with enough time to enter the protected area
and disarm the system. To program the Entry Delay 1 Timer, key in the desired 3-digit delay value (000 to 255
seconds, Default = 45 seconds) into section [710]. Entry delay zones are commonly used at the entry/exit points of the
protected area (i.e. front/back door, garage, etc.). Using different entry delays is useful when, for example, one entry
point requires a longer delay than the other entry point or in a partitioned system where each partition may require a
different entry delay.
5.1.2 Entry Delay 2 Zones
Sections [001] to [032]: Zones 1 to 32, First Digits = 02
Entry Delay 2 zones are identical to the Entry Delay 1 zones, except it uses a separate entry delay timer. To program
the Entry Delay 2 Timer, key in the desired 3-digit delay value (000 to 255 seconds, Default = 45 seconds) into section
[711].
Wireless Keypad Hardwire
Zone 1 Yes Yes Yes (Input Z1)
Zone 2 Yes Yes Yes (Input Z2)
Zone 3 Yes Yes Yes (Input Z1 with ATZ)
Zone 4 Yes Yes Yes (Input Z2 with ATZ)
Zone 5 to 32 Yes Yes No
Section Zone Definition Partition Assignment Zone Options
[001] = Zone 1 _____/_____ _____________ 1 2 3 4 5 6 7 8
[032] = Zone 32 _____/_____ _____________ 1 2 3 4 5 6 7 8
Zone Definitions
00 = Zone disabled
01 = Entry Delay 1
02 = Entry Delay 2
03 = Entry Delay 1/Stay/Sleep
04 = Entry Delay 2/Stay/Sleep
05 = Follow
06 = Follow /Stay
07 = Follow/Stay/Sleep
08 = Instant
09 = Instant/Stay
10 = Instant/Stay/Sleep
11 = Instant Fire
12 = Delayed Fire
13 = Instant Fire Silent
14 = Delayed Fire Silent
15 = 24Hr. Buzzer
16 = 24Hr. Burglary
17 = 24Hr. Hold-up
18 = 24Hr. Gas
19 = 24Hr. Heat
20 = 24Hr. Water
21 = 24Hr. Freeze
Zone Options
[1] = Auto-zone Shutdown
[2] = Bypassable Zone
[3] = RF Supervision
[4] [5]
OFF OFF Audible Alarm
OFF ON Pulsed Alarm
ON OFF Silent Alarm
ON ON Report Only
[6] = Intellizone
[7] = Delay alarm transmission
[8] = Force Zone
Partition Assignment
[1]- Partition 1
[2]- Partition 2
[3]- Both partitions