MG5000 19
5.4.5 Intellizone
Sections [001] to [032]: Zones 1 to 32
Option [6] OFF = Intellizone Disabled (default)
Option [6] ON = Intellizone Enabled for Selected Zone
This feature reduces the possibility of false alarms. When a zone with the Intellizone option opens, the panel does not
immediately generate an alarm. First it triggers the Intellizone Delay Timer. To program the Intellizone Delay Timer, key
in the desired 3-digit value (000 to 255 seconds, Default = 48 seconds) into section [713]. If any of the following
conditions occur during this period, the panel will generate an alarm:
During the Intellizone Delay, a second zone has caused an alarm.
During the Intellizone Delay, the zone in alarm has restored (closed) and re-occurred (opened).
The zone in alarm remains open for the entire Intellizone Delay.
5.4.6 Delay Alarm Transmission
Sections [001] to [032]: Zones 1 to 32
Option [7] OFF = Delay Alarm Transmission Disabled (default)
Option [7] ON = Delay Alarm Transmission Enabled for Selected Zone
When an alarm condition occurs on a zone with this option enabled, the control panel enables the bell/siren output, but
does not report the alarm to the monitoring station until the end of the Delay Alarm Transmission. To program the
Delay Alarm Transmission, key in the desired 3-digit delay value (000 = Disabled, 001 to 255 seconds) into section
[833]. During this period, disarming the system disables the bell/siren output and cancels the report code
transmission. This feature is commonly used with entry delay zones to reduce false alarms created by new users who
may not disarm the system in time.
5.4.7 Force Zones
Sections [001] to [032]: Zones 1 to 32
Option [8] OFF = Force Zone Disabled
Option [8] ON = Selected Zone is Force Enabled (default)
Any open Force Zones at the time of arming will be considered deactivated by the control panel. If during this period a
deactivated zone is closed, the control panel will revert that zone to active status. Consequently, the control panel will
generate an alarm if the zone is breached.
Do not program a fire zone with the Force option, as the control panel will never bypass fire zones
when Force arming.
5.5 EOL Zones
Section [706]: Zone Options
Option [2] OFF = Zones do not use EOL resistors (default)
Option [2] ON = Zones require EOL resistors
If all detection devices connected to the control panel have input terminals that require 1K end of line resistors, enable option
[2] in section [706]. For details on using EOL resistors, see Single Zone Inputs on page 6.
5.6 ATZ Zone Doubling
Section [705]: General Zone Options
Option [1] OFF = ATZ zone doubling disabled (default)
Option [1] ON = ATZ zone doubling enabled
Enabling ATZ Zone Doubling allows you to install two detection devices per input terminal.
5.7 ATZ Wiring Options
Section [705]: General Zone Options
Option [2] OFF = ATZ Series (default)
Option [2] ON = ATZ Parallel doubling enabled
ATZ Zone Doubling can be configured in either a series or parallel connection.
5.8 Zone Input 1 Becomes a 2-wire Smoke Input
Section [706]: General Zone Options
Option [3] OFF = Zone input 1 is a standard zone input (default)
Option [3] ON = Zone input 1 becomes a 2-wire smoke input
With this option enabled, zone input 1 becomes a 2-wire smoke input.