Part 8: Alarm Options
8.1 Bell Cut-Off Timer
Section [747] = Partition 1, [748] = Partition 2
000 = Disabled, 001 to 255 minutes, Default = 4 minutes, 5 minutes minimum for ULC installations
After an audible alarm, the bell or siren will stop upon disarming of the partition or when the Bell Cut-Off Timer has elapsed,
whichever comes first.
8.2 Recycle Alarm
After the Bell Cut-Off Timer and the Recycle Delay have elapsed, the control panel will re-verify the zone status. If there are any
open zones, the control panel will generate another alarm. In one armed period, the control panel will repeat this sequence the
number of times defined by the Recycle Counter.
8.2.1 Recycle Alarm Delay
Section [714]
000 = disabled, 001 to 255 minutes, Default = Disabled
The Recycle Delay determines the amount of time after Bell Cut-Off that the control panel will wait before re-verifying
zone status.
8.2.2 Recycle Alarm Counter
Section [715]
000 = disabled, 001 to 255, Default = Disabled
The Recycle Counter determines the number of times the control panel will re-verify the zone status after Bell Cut-Off
in one armed period.
8.3 Tamper Recognition
8.3.1 Zones/RF Module and Keypad/Bus Module Tamper Recognition
Section [705]: Tamper Recognition Options
If a device has been tampered with (i.e. the anti-tamper switch has been set off), the Magellan MG5000 can generate
a trouble, an alarm, and/or transmit a report code to the monitoring station. The system will react to an RF zone and a
keypad/bus module differently.
8.4 RF and Keypad/Bus Module Supervision
Section [705]: Supervision Options
The Magellan MG5000 waits for each of its assigned wireless transmitters to send a status signal within a specified time period to
confirm their presence and functionality. If a device has not sent a signal within that time period, the Magellan MG5000 can
generate a trouble, an alarm, and/or transmit a report code to the monitoring station. The system will react to an RF zone and a
keypad/bus module differently.
[3] [4] Zones/RF Module Tamper Recognition Options Keypad / Bus Module Tamper Recognition Options*
OFF OFF Disabled
TROUBLE ONLY
OFF ON TROUBLE ONLY TROUBLE ONLY
ON OFF When disarmed: TROUBLE ONLY
When armed: Follow zone’s alarm type
TROUBLE ONLY
ON ON When disarmed: AUDIBLE ALARM
When armed: Follow zone’s alarm type
AUDIBLE ALARM
* Tamper recognition of keypad/bus module only if section [700] option [7] is enabled.
[6] [7] RF Supervision Options Keypad / Bus Module Supervision Options
OFF OFF Disabled Disabled
OFF ON
TROUBLE ONLY TROUBLE ONLY
ON OFF When disarmed: TROUBLE ONLY
When armed: Follow zone’s alarm type
TROUBLE ONLY
ON ON When disarmed: AUDIBLE ALARM
When armed: Follow zone’s alarm type
AUDIBLE ALARM